EN Global Delivery
KNMKS Dynamic Automation Supply logo Request a Quote

KNMKS Technical Blog

HMI Backup Handover: Keep the Complete Restore Set

A backup's main filename is not proof of a complete recovery package. Preserve the file set, identify its purpose and keep engineering records separate.

HMI Backup Handover: Keep the Complete Restore Set

A replacement panel can arrive on time while its recovery files remain incomplete. Before treating “backup available” as a closed item, establish what the retained files are intended to do and whether the whole documented package has survived the handover.

This article focuses on file custody before an HMI replacement, rather than repeating our broader HMI compatibility guide. It does not authorize a restore, download or change to an operating machine.

A specific example: one backup, several files

Siemens’ Unified Basic Panels V21 backup and restore documentation describes a package containing a master file with the extension .brf and associated files with numbered extensions such as .0 and .1. The number of associated files varies. The manual warns that missing a required file prevents loading the backup, and that renaming the saved backup files makes them unusable for that restore function.

The important boundary is the named product family and procedure. This is not a claim that every Siemens panel, or every HMI manufacturer, uses this file layout. It demonstrates why one familiar filename is not sufficient evidence that a recovery package is complete.

Identify the purpose before tidying the folder

Ask the project owner to distinguish an editable engineering archive, a device-restoration backup, and separately retained operational data. A folder named “HMI project” does not identify which of these it contains. Record the producing tool and version, device reference, creation date and intended use before deciding which artifact supports the planned work.

Do not rename internal files to make a package look like an engineering project, combine files from different backups, or discard unfamiliar companion files as duplicates. Keep the original package unchanged and put explanatory notes in a separate handover record. Whether an artifact supports editing or migration must be established with the relevant engineering environment and documentation, not guessed from its extension.

Make a small handover record outside the package

Record Useful evidence What it does not prove
Origin Device identity, responsible owner and the documented backup method. That a similarly named folder belongs to the same machine.
File inventory Original relative filenames, file count and byte sizes for the retained set. That only the main file is needed.
Copy verification A checksum comparison against a controlled reference copy where available. That the source was current, complete or tested for restoration.
Acceptance status Who reviewed the package and any outstanding recovery questions. That receiving the files approves loading them onto a panel.

This is a recommended custody record, not a Siemens backup format. A matching checksum helps compare copies; it cannot supply a missing file or turn an unidentified package into a validated recovery route.

File integrity and target suitability are separate gates

Siemens’ WinCC V20 backup and restore guidance for the listed panel families says to use the project-data restore function only on devices configured using the same configuration software. Consult the exact device and software documentation for the intended source and target. A complete file set is not, by itself, approval to restore it onto a different terminal.

For example, a request for a Siemens 6AV2123-2JB03-0AX0 reference identifies a hardware item. It does not establish that the Unified Basic file layout above applies to that item, or that the site’s retained backup is usable with it. Keep the product reference and the confirmed recovery method linked, but do not substitute one for the other.

Resolve uncertainty before scheduling the outage

If only a master file has been retained where a documented multi-file package is required, mark the recovery set as incomplete and ask the authorized owner for the original set. Do not manufacture missing files or test an uncertain package by restoring it to production equipment. Qualified personnel should plan any validation under the site’s approved procedures while preserving the original records.

For a hardware inquiry, review the HMI and Displays category and send KNMKS the exact panel reference, quantity, destination and whether the recovery route has been confirmed. State unresolved file or project questions explicitly. Do not send passwords or plant application files through an ordinary inquiry without authorization and an approved secure channel. Availability, condition, delivery and application suitability require separate confirmation.

Image note: the featured image is an AI-generated generic maintenance illustration, not the linked Siemens product or evidence of an approved recovery procedure.

Related Product Paths

Continue from this article into KNMKS system and product pages.

System hub Automation Systems System hub Industrial Control Systems Product archive All Products

Continue Reading

Related automation notes

View All Articles →